E
Communication Standard
Module Type
Network Type
Standard
Media Access
Communication Method
Communication Cable
Communication Distance
I/O Data Length
Communication Parameter Setting*
Configuration Tool*
Category
TRIOU
Slave
Profibus-DP
EN50170 / DIN 19245
Master-Slave (passive station)
Bus
Shielded Twisted Pair
1200m (9.6k ~ 187kbps)
400m (500kbps)
200m (1.5Mbps)
100m (3M ~ 12Mbps)
32byte
Note (Setting its parameter through GMWIN high-speed link and Sycon)
Note (Sycon)
Profibus is selected, applied, and produced independently by the manufacturer (Vender-independence). It is approved
for venders independence and openness according to Profibus standard EN50170 which is a open field-bus standard
that is extensively used in a process automation. Among them, DP is the most commonly used communication profile. It
is applicable for Master-Slave communication between Master automation device which has a device level and decentrali-
zed slave I/O device to optimize the communication speed and price with the network which is suitable for FA service
condition of Field Level.
For more details on Profibus-DP, please refer to ‘‘Korean Profibus Association’’ Homepage.
( http://www.profibus.co.kr)
Profibus - DP Communication Introduction
Note. * Support through LSIS GM3/4/6 master modules.(G3L-PUEA/G3L-PUEB/G4L-PUEA/G4L-PUEB)
* When using other manufacturers masters, use applicable parameter tool and configuration tool.