XGB Analog edition manual 
 
 
13.13.3  Check and Measure the breakdown 
 
 
 
1) The LED is turned off. 
 
The LED is turned off.
The analog module is installed on 
correct position.
Install the analog module correctly.
No
Yes
I/O information is shown in XG5000 
software.
Call our near agency or A/S center.
No
Yes
When the abnormal analog input 
module is changed into normal one, 
it operates well.
Yes
Call our near agency or A/S center.
 
 
 
 
2) The LED is flickering. 
 
The LED is flikering.
The LED is flikering 1s intervals.
The wiring is normal.
Make wiring correctly by referring the 
instructions.( Check disconnection)
No
Yes
The parameter setting is correct.
(Check 'PUT' )
The operation parameter is error.
Set correctly by referring parameter setting 
rules from instructions.
(Check error code)
 
 
13 - 46