XGB Analog edition manual   
15 - 4 
 
 
At this system, we assume that the PID parameter is specified as shown below to describe the PID control 
operation. 
 
Output temperature of 
heating system (PV) 
Proportional coefficient 
(K
P
) 
                                                    <Table 15.1 example of control of heating system> 
 
At  this  system,  if  we  assume  that  target  value  of  output  temperature  is  50℃  and  initial  value  of  output 
temperature is 0℃, SV and PV becomes 50 and 0 respectively. In case of this, PID controller acts as follows. 
 
(3) Proportional control (P control) 
In the proportional control, the controller yields output that is proportional to error.   
Manipulated value of controller by Proportional control is as follows. 
 
                                      (15.2.8) 
 
(a) If P control starts, output of controller by initial P operation is as follows.   
 
 
 
If P control is executed for 10 seconds, output temperature will be as table 15.2. 
If this is expressed with graph, it will be as Figure 15.2.   
 
                                           
< Table 15.2 example of Proportional control >