MXD70 Setpoints, Current Outputs, and
Digital Inputs Configuration Guide
Dose Alarm Acknowledge
To cancel the dose alarm and reactivate the setpoint,
select the required setpoint from the shown list and
press enter.
Note – If, once reset, the setpoint again remains
energised for the length of the dose alarm timer then
the dose alarm will once again activate. If this
problem persists then a dosing problem will need to
be investigated.
/ – Select Option
EXIT
– Cancel
– Save Selection
Initial Charge
This allows the user to have a one time over-ride of
the Dose Alarm to use for example when filling a tank
for the first time.
The user enters a charge time and then initiates the
charge time. The unit will then disable the dose alarm
until either the relay becomes inactive because the
setpoint has been reached or the charge timer
reaches zero in which event the unit will
automatically display a Dose Alarm.
/ – Select Option
EXIT
– Cancel
– Save Selection
Charge Time
Sets the initial charge time.
/ – Increase / Decrease Digit
– Select Next Digit
EXIT
– Cancel
– Save Value