LUKO’s FD-S & FD-X Series
DUCTED DEHUMIDIFIER
User’s Manual
KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE
Thank you for choosing our dehumidifier. This owner’s manual will provide you with
valuable information necessary for the proper care and maintenance of your new
dehumidifier. Please take a few moments to read the instructions thoroughly and
familiarize with all the operational aspects of this dehumidifier. This unit removes
excessive moisture from the air to create a more comfortable environment.

Questions and Answers

  • M
    markbarreraAug 9, 2025
    Why is my LUKO Dehumidifier not performing as expected?
    • S
      seanyoungAug 9, 2025
      If your LUKO Dehumidifier isn't dehumidifying as expected, several factors could be at play. The air temperature or humidity might have dropped. The humidity level on the controller may need calibration. The unit could be in a defrost cycle. A dirty or clogged air filter can also reduce performance. There might be a low refrigerant charge due to leaks, or air leaks in the ducting. In some cases, the compressor may be damaged, or the air duct isn't properly installed, leading to insufficient air volume.
  • P
    Pamela WrightAug 15, 2025
    Why is my LUKO Dehumidifier not turning on?
    • J
      James GonzalezAug 16, 2025
      If your LUKO Dehumidifier isn't operating, with no fan, compressor, or controller power, consider these potential causes: 1. The device isn't plugged in or lacks power supply. 2. The controller is damaged. 3. Internal wiring is poorly connected. 4. The 3 Phase Protector is faulty, or the phase sequence is incorrect. 5. There's a voltage failure. 6. The Low Pressure Switch is activated, possibly due to gas leakages. Check gas pressure with a refrigerant gauge manifold and inspect the heat exchanger and copper tubes for leakage points if pressure is low.
  • T
    trevorrobbinsAug 21, 2025
    What causes evaporator coils to freeze on my LUKO FD-X Dehumidifier?
    • R
      Roger WhiteAug 21, 2025
      If the evaporator coils in your LUKO Dehumidifier are constantly frosting and dehumidification capacity is low, consider these possibilities: * There may be a refrigerant shortage due to leakages. * The air filter(s) might be too dirty, restricting airflow, or the duct connection is improper. * The filter drier could be blocked and require replacement.
  • M
    Michael DaviesAug 27, 2025
    How to troubleshoot a LUKO Dehumidifier fan that won't rotate?
    • A
      Alicia MannAug 27, 2025
      If the fan in your LUKO Dehumidifier isn't rotating when the ventilation function is on, and the compressor starts and stops frequently, eventually ceasing to run, check the following: 1. Ensure there are no obstructions preventing the fan from rotating. 2. Check the Controller Pin No.2 for DC Voltage output of 0 – 10V. 3. Verify that the Controller Pin No. 1 (com/gnd) is properly connected. 4. If there's no DC output after checking the controller, replace it. 5. The fan bearing might be worn out. 6. The fan not running could lead to voltage protection. 7. The fan might be faulty.
  • M
    Mr. Phillip HudsonSep 2, 2025
    Why is the fresh air damper on my LUKO FD-X Dehumidifier not working?
    • R
      Ryan MontoyaSep 2, 2025
      If the fresh air damper on your LUKO Dehumidifier isn't working, check these potential issues: 1. The connection to the damper may not be properly connected. 2. There might be a loose connection in the ventilation control circuit. 3. A loose connection in the damper power circuit could be the cause. 4. The fresh air damper itself might be defective.

Summary

1 SAFETY INTRODUCTION

1.1 Safety

This series of dehumidifier is in conformance with all provisions of European security requirements and standards, the safety of worker and equipment are taken into care...

2 INTRODUCTIONS OF DEVICE

2.2.6 Protection devices

Dehumidifier controller is specially designed according the operation of the dehumidifier and it is designed to optimize its performance.

3 INSTALLATIONS

3.11 Electrical connection

Be careful! All electrical connection works must meet local electrical equipment installation standards, done by qualified professionals.

4 OPERATIONS

4.1 Controller Terminals

Description of the various terminals on the dehumidifier's controller and their functions.

4.2 Controller Interface

Explanation of the dehumidifier's controller display and button functions.

4.3 Parameters Setting

Guide to setting general and factory parameters for the dehumidifier.

4.5 Mode; Function

Overview of dehumidification working modes and their operational functions.

4.6 Parameters Code; Function

Humidity and Temperature Parameters

Details on setting humidity, temperature, and air damper parameters.

4.7 Working Status Display

4.8 Error Code

Error Code List

List of error codes and their corresponding descriptions.

4.9 Error Code Address

4.10 Safety Cautions

General Safety Precautions

Important safety advice regarding moving parts, sensors, wiring, and cleaning.

5 MAINTENANCES

5.4.1 Maintenance during start of usage season

Filter Maintenance Schedule

5.5 Inspection and maintenance procedures

Safe relocation of machines

Important notes on refrigerant handling and safety during installation or relocation.

Refrigerant handling during installation;repair

Precautions for refrigerant circuit management during relocation or repair.

Installation Safety Precautions

Warnings against installing in corrosive environments and improper wiring.

6. Troubleshooting

Common Issues Requiring Support

Cases like harsh sound, tripped switches, or hot power cords needing LUKO support.

General Troubleshooting Precautions

Safety steps before troubleshooting, like turning off power and allowing cooling.

No Dehumidification - Fan;Compressor Not Running

Troubleshooting steps for no operation due to power, controller, or wiring issues.

No Dehumidification - Fan Running, Compressor Not

Steps for issues where the fan runs but the compressor does not.

Fan Not Rotating or Frequent Compressor Cycling

Troubleshooting for fan rotation problems or compressor short-cycling.

Evaporator Frosting and Low Capacity

Causes and solutions for evaporator frost and reduced dehumidification.

7 APPENDIX

LUKO FD-X Series Specifications

General IconGeneral
BrandLUKO
ModelFD-X Series
CategoryDehumidifier
LanguageEnglish