Description
Hex Decimal
Dev Addr
03 03
Func Code
10 16
Number of bytes
28 40
Value 1 (Nov 4)
48,6A,B4,80 240338
Value 2 (Nov 5)
48,6A,AD,40 240309
Value 3 (Nov 6)
48,6A,AA,C0 240299
Value 4 (Nov 7) 48,6A,B6,40 240345
Value 5 (Nov 8) 48,6A,B1,40 240325
Value 6 (Nov 9) 48,6A,B4,80 240338
Value 7 (Nov 10) 48,6A,B7,40 240349
Value 8 (Nov 11) 48,6A,AF,C0 240319
Value 9 (Nov 12) 48,6A,B3,40 240333
Value 10 (Nov 13) 48,6A,BD,C0 240375
CRC
A9,2A
Response:
The response to the load profile query contains device
address, function code and number of bytes data each
of 1 byte, and then the requested parameters of 4 bytes
each. Each parameter represents data over a period of a
day when daily log is accessed and represents data over
a period of a month when monthly log is accessed.
The response ends with 2 byte CRC.
Note: If a user tries to access the data which is out of the range of the datalog i.e. more than 1 year before the
present date for daily log and more than 14 years before the present date for monthly log, it will result in a modbus
exception. The same will occur if a user tries to access the data before the starting date of the corresponding log or
a future date.
5. Connection for Optional Pulse Output / RS 485
(rear view of Multifunction Meter):
2. USB and RS 485 Output with Relay1 &
Relay2
B A
Gnd
RS 485
NO
Relay 1
COM NO COM
Relay 2
USB
1. RS 485 Output with Relay1 & Relay2
B A
Gnd
RS 485
NO
Relay 1
COM NO COM
Relay 2
55