EasyManua.ls Logo

LUMINELL RLX CxZ1.21 - ELECTRICAL INSTALLATION; CABLE CONNECTIONS; Dimming Connection

Default Icon
9 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Luminell Norway AS Doc. Nr.: D0011 RLX CxZ1.21 User Manual v1.5
Page 5 of 9
9 ELECTRICAL INSTALLATION
Risk of electric shock. Ensure that power is disconnected before carrying out any connections.
Both the power and dimming connection can be parallel (or in-line) connected. If so, ensure
to use suitable cables due to the increased current running through the junction box and
spring terminals.
9.1 CABLE CONNECTIONS
9.1.1 Dimming Connection (slot 7-10)
On the positive and negative DIM wire connection, it is possible to control the floodlight in three different
ways. The dimming range is approx. from 10% up 100% light output.
Interface
All on the same
connection: DIM +/-
Signal specifications
Comment
Resistance
One floodlight: 0-100 kΩ
Several floodlights(n) parallel connected: 100 kΩ/n.
Eg. 4x floodlight controlled together would require a
25 kΩ variable resistor or potentiometer.
It is recommended to use logarithmic resistors, since
the sensitivity is greatest when resistance is small. If
nothing is connected the output is 100%
Very simple to set up. Requires
no external electronics, only
cable and a variable or fixed
resistor(s). Resistant to
electromagnetic disturbance.
0-10 V
External low voltage supply up to 10 VDC.
Very common method for DIM
control. The RLX CxZ1.21 has a
built-in delay for stable and
reliable control and resistance
to electromagnetic
interference.
4-20 mA
External constant current source. Adjusting the
current from 4-20mA at a nominal voltage of 24
VDC. Only one floodlight per 4-20mA controller.
Not affected by
electromagnetic disturbances.
9.1.2 Startup current
A startup current is needed to energize the electronics inside the RLX CxZ1.21 LED floodlight. When using a
MCB16 Type C fuse, approx. 20 RLX CxZ1.21 floodlights can be started at once. The inrush current is the
equal for all power alternatives.
Function
Symbol and position
Nr.
Description
Wire cross section
Power Grid
Connection
L (1,2)
Phase
0,2 <6mm
2
N (3,4)
Neutral
conductor
0,2 <6mm
2
PE (5,6)
Earth
connection
0,2 <16mm
2
DIM connection
See 9.1.1
DIM + (7,9)
Positive DIM
0,1 <2,5mm
2
DIM - (8,10)
Negative DIM
0,1 <2,5mm
2
ONLY Luminell
battery backup
Acc. Connection
(Separate
product)
+ (11)
LED/PSU
positive
0,1 <2,5mm
2
- (12)
LED/PSU
negative
0,1 <2,5mm
2
C (13)
Control signal
0,1 <2,5mm
2
N (14)
Temperature
sensor
0,1 <2,5mm
2
More illustrations in appendix

Related product manuals