CDA3000 Operation Manual
4-7
4  Commissioning
1
2
3
4
5
A
DE
EN
FR
IT
ES
FR
VFC commissioning, rotational 
drive without encoder
Prerequisite:
• Inverter module fully connected.
• Recommended IEC standard motor (see section A-1) connected.
• Control terminals wired according to 
terminal assignment 2,
 
see page 3-14.
•A K
EYPAD or a PC with installed DRIVEMANAGER (version V2.3 or 
higher) is connected. For operation see section 4.6 and 4.7.
Attention: Make sure the rotating drive in your machine cannot cause 
any damage (e.g. overrunning its stop limit) during commis-
sioning.
  
 
Step Action Comment
1
Switch on the power to the 
inverter module.
After power-up the inverter module per-
forms a self-test (lasting approx. 1... 3 s).
2
In subject area _15FC set parame-
ters
152-ASTER to ROT_1
ROT_1 = Control terminal assignment 
Analog speed input,
MOP function
3
Check that your drive can be run 
at the rotating field frequency and 
with the ramps as per the factory 
setting.
Rotating field frequency (FMAX) = 50Hz 
with reference (R1) = 10 V
Acceleration ramp = 20 Hz/s
1)
Deceleration and stop ramp = 20 Hz/ s
1)
If this is not possible, change the 
parameters shown adjacent. 
Back-up the setting in subject 
area _15FC with
parameter 150-SAVE.
Subject area/Parameter
FMAX _30OL 303 -FMAX1
Acceleration
ramp _59DP 590 -ACCR1
Deceleration
ramp _59DP 592 -DECR1
Stop ramp _59DP 594-STPR1
1
Close ENPO contact and set a low 
reference value with pot R1.
ENPO active enables power stage.
2
Start drive by closing the STL or 
STR contact.
STL = Start counter-clockwise
STR = Start clockwise
3
Check direction of rotation of motor 
shaft.
If direction is wrong check motor 
connection (phase sequence).
4
Brake drive by opening the start 
contact.
Drive brakes down to a standstill.
5
Open ENPO contact.
ENPO inactive safely disables power 
stage.
Commissioning is complete.
1) Factory setting from BG1 
to BG5 (15 kW ) = 20 Hz/s, as 
from BG6 (22 kW) to 
BG8 = 5 Hz/s
Start drive
Remember to
save the set-
ting.
• Call up subject area 
_15FC
• Select parameter 
150-SAVE
• Set parameter to 
START and confirm