4-14
CDA3000 Operation Manual
4  Commissioning
Testing the encoder connection 
Regulated test run
 
Step Action Comment
1
Open ENPO contact. Power stage safely disabled.
2
Rotate motor shaft clockwise by hand 
(1) Direction of view,
(2) Clockwise.
Clockwise is indicated on the display 
of the KP200.  If not, check the 
encoder connections.
If direction of rotation matches display, test is complete.
Step Action Comment
1
In subject area _15FC enter motor 
data (refer to motor name plate) and 
confirm.
Rated power [kW]
154-MOPNM
Rated voltage [V]
155-MOVNM
Rated frequency [Hz]
156-MOFN
Rated speed [rpm]
157 -MOSNM
Rated current [A]
158-MOCNM
cos ϕ of motor
159-MOCOS
2
Close ENPO contact, set parameter 
163-ENSC to START.
Automatic motor identification 
started, lasts approx. 3-4 min., then 
automatically jumps to STOP.
3
Select parameter 300-CFCON, set to 
FOR, confirm.
Control mode 
Field-Oriented Regula-
tion (FOR)  
selected.
4
Select subject area _79EN and with 
parameter 790-ECLNC set the lines 
per revolution of the encoder.
Lines per revolution - see page 3-17 
"Encoder" and name plate of 
encoder/motor
5
Back-up the setting in subject area 
_15FC with parameter 150-SAVE.
Back-up device setup, then jumps 
automatically to READY.
6
Start drive by closing the STL or STR 
contact.
Motor accelerates to preset refer-
ence.
7
Brake drive by opening the start con-
tact.
Drive brakes down to a standstill.
8
Open ENPO contact.
ENPO inactive safely disables power 
stage.
The regulated test run is complete.
start
enter
stop
return
VAL
Hz