4-4
CDA3000 Operation Manual
4 Commissioning
4.2.2 Serial commis-
sioning with
D
RIVEMANAGER
Prerequisite:
All inverter modules are fully connected.
The first drive is already fully commissioned.
A PC with installed D
RIVEMANAGER user software (V2.3 or higher) is
connected.
For additional information refer to the DRIVEMANAGER HELP.
Step Action Comments
1
Connect your PC to the inverter
module of the first drive and switch
on the power to the inverter.
Use a standard serial cable (9-pin
D-SUB, pin-and-socket) e.g. LUST
accessory CCD-SUB90x .
2
START DriveManager.
Automatically connects to the linked
inverter module.
If the connection fails, check the settings in the Tools > Options menu and
try again by clicking on the icon .
3
Save the current data set by clicking
on the icon ,
either in the parameter database
(directory: c:/../userdata) of the
D
RIVEMANAGER or to a floppy disk
(a:/).
Clicking on the icon always saves the
current data set of the connected
device.
Assign the file a name of your choice.
4
Connect your PC to the inverter module of the next drive and switch on the
power to the inverter.
5
Click on the icon to connect
between the D
RIVEMANAGER and the
now connected device.
6
Click on the icon to load the
data set saved in step 4 into the
device.
The data set is filed in the device as
user data set 1.
7
Back-up the setting in subject area
_15FC with parameter 150 -SAVE
Repeat steps 4 ... 7 on each additional drive.
Saving a data set from the
device to a file
Loading a data set from a file
into the device
Remember to
save the set-
ting.
Call up subject area
_15FC
Select parameter
150-SAVE
Set parameter to
START and confirm