4-10
CDA3000 Operation Manual
4 Commissioning
Start drive
5
Close ENPO contact, set parameter
163-ENSC to START.
Automatic motor identification started,
lasts approx. 3-4 min., then automati-
cally jumps to STOP.
6
Select parameter 300-CFCON, set
to SFC, confirm.
Control mode:
Sensorless Flux Control
(SFC) selected
7
Back-up the setting in subject area
_15FC with parameter 150-SAVE.
Step Action Comment
Step Action Comment
1
Close ENPO contact. Enables power stage.
2
Start drive by closing the STL or STR
contact.
STL = Start counter-clockwise
STR = Start clockwise
3
Check direction of rotation of motor
shaft.
If direction is wrong check motor
connection (phase sequence).
4
Brake drive by opening the start
contact.
Drive brakes down to a standstill.
5
Open ENPO contact. Safely disables the power stage.
Commissioning is complete.