EasyManua.ls Logo

Lutron Electronics MAESTRO MS-VPS2 - Wiring Diagrams (continued); Wiring Diagram 3: 3-Way Installation (120 V~) without Neutral

Lutron Electronics MAESTRO MS-VPS2
23 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maestro Sensor
369666f 11 09.05.19
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy / Vacancy Sensor
Wiring Diagrams (continued)
1
When using controls in single location installations, tighten the blue terminal or cap blue wire. Do not connect the blue terminal / wire to any other
wire or to ground.
2
Only one occupancy sensor switch can be used per multi-location circuit.
3
A single standard mechanical 3-way switch or up to 9 companion switches may be connected to most occupancy sensor switches.
Standard mechanical 3-way switch cannot be combined with companion switch. Total blue terminal wire length may be up to 150ft (46m).
Note: Connect green-sleeved wire to ground only in retrofit and replacement applications.
Continued on next page...
Black
Blue
Green-sleeved wire
Ground
Green
screw
Ground
120 V~
50 / 60 Hz
Hot/Live
Neutral
Load
Standard
mechanical switch
Black
Jumper wire
Bare
Different color
screw (Common)
OR
Black
Blue
Ground
Green-sleeved wire
Ground
120 V~
50 / 60 Hz
Hot/Live
Neutral
Load
Standard
mechanical switch
Black
Jumper wire
Bare
Different color
screw (Common)
Green
screw
3-way Installation with Standard Mechanical Switch (120 V~)
2, 3
-OPS5M, -OPS6M2-DV, -VPS5M, -VPS6M2-DV
Wiring Diagram 3 - without Neutral
Occupancy
sensor switch
Occupancy
sensor switch
11

Other manuals for Lutron Electronics MAESTRO MS-VPS2

Related product manuals