PowerPool™
Electrical Requirements:
240 volt, 60 Hz, single phase, 50 or •
60 amp., 4-wire service (line 1, line 2,
neutral, and ground or,
*40 Amp Option
Note: The heater can be activated only with
the pump on low speed. Only the spa light
can be operating at the same time without
disabling the heater. See your authorized
MAAX Spas dealer to select this option.
Spas installed for 240 volt, 60 Hz, single
phase operation require a 4-wire, 50 or 60
amp 240 volt sub-feed in non-metallic pipe
to the spa equipment compartment (line 1,
line 2, neutral and ground). A green colored
terminal (or wire connector marked “G”,
or “GR”, or “Grounding”) is provided in the
control box. To reduce the risk of electrical
shock, connect this terminal or connector
to the grounding terminal of your electrical
service or supply panel with a continuous
green insulated copper wire equivalent to
the circuit conductor supplying this equip-
ment, but no smaller than No. 12 AWG. A
second pressure wire connector is provided
on the surface of the control box for bond-
ing to local ground points. To reduce the
risk of electrical shock. this connector should
be bonded with a No. 6 AWG copper wire to
any metal ladders, water pipes, or any metal
within 5 feet of the spa.
Note: Copper wire is strongly recommend-
ed for all electrical connections.