Adress Hex Bit Meas.
Point
Description Unit Origin Signal
range
MW 118 76 0
1
2
3
10
11
12
15
CAN-1 error
CAN-2 error
CAN-3 error
Communication error to DM
Emergency generator mode
MDO used
HFO used
Live-Bit (status changes at least every 5 seconds)
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
binary
binary
binary
binary
binary
binary
binary
binary
MW 119 77 0
1
2
3
4
5
6
7
Shutdown : HT cool. water temp. engine outlet high
Shutdown overridden :
HT cool. water temp. engine outlet high
Shutdown : Lube oil pressure filter outlet low
Shutdown overridden : Lube oil press. filter outl. low
Shutdown : Engine overspeed
Shutdown : Actuator Error
Shutdown : Double Pick-Up Error
Shutdown : Stop failure
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
binary
binary
binary
binary
binary
binary
binary
binary
MW 120 78 0
1
2
3
4
5
6
7
8
9
10
Shutdown : HT cool. water temp. engine outlet high
Shutdown overridden :
HT cool. water temp. eng. outlet high
Shutdown : Lube oil pressure filter outlet low
Shutdown overridden : Lube oil press. filter outl. low
Shutdown : Engine overspeed
Shutdown : OMD
Shutdown overridden : OMD
Shutdown : CCMON
Shutdown overridden : CCMON
Shutdown : Emergency stop active
Shutdown : Remote Shutdown
DM
DM
DM
DM
DM
DM
DM
DM
DM
DM/
CMS
DM
binary
binary
binary
binary
binary
binary
binary
binary
binary
binary
binary
MW 121 79 0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
Alarm : HT cooling water temp. engine outlet high
Alarm : Lube oil pressure filter outlet low
Alarm : Engine overspeed
Alarm LAH28 : Lube oil level high
Alarm LAL28 : Lube oil level low
Alarm LAH42 : Fuel oil leakage
Alarm FE94 : Cylinder lubrication no flow
Alarm LAL98 : Alternator cooling water leakage
Alarm : Start failure
Alarm PAL25: Prelub. Oil pressure low
Alarm : Startpreparation failure
Alarm : Engine running error
Alarm PAL01 : L.T. cooling water pressure low
Alarm PAL10 : H.T. cooling water pressure low
Alarm PDAH21-22 : Diff. pressure lube oil filter high
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
CMS
binary
binary
binary
binary
binary
binary
binary
binary
binary
binary
binary
binary
binary
binary
binary
MAN Diesel & Turbo
B 19 00 0
Modbus list
3700054-4.0
Page 4 (5)
L27/38S, L16/24S, L21/31S, L16/24, L21/31, L27/38
2015.11.27

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Man L23/30DF and is the answer not in the manual?

Man L23/30DF Specifications

General IconGeneral
BrandMan
ModelL23/30DF
CategoryPortable Generator
LanguageEnglish

Related product manuals