66 Part Number 040005626 5/17
Safety Limit 3
The harvest float switch hasn’t opened for 10
continuous seconds within 4 minutes of the water
inlet valve energizing.
Possible Cause Checklist
Improper installation
Refer to “Installation/Visual Inspection Checklist”
on page 55.
Water System
Water dump valve
Harvest float valve dirty or defective
Low water pressure (20 psig min.)
Dirty defective water filter (when used)
Loss of water from sump area
Dirty/defective water inlet valve
Electrical system
Water inlet valve coil defective
Harvest float valve defective