52 Part Number 000015433_05 3/21
Contactor Closed?
Line Voltage To
Compressor?
YES
YES
NO
YES
NO
Verify:
Compressor Overload is Closed
Start Components Function
Fan Cycling Control Functions
Condenser Fan Motor Functions
Water cooled only:
Water Regulating Valve Functions
Repair Wiring
Replace Contactor
Line Voltage To
Compressor Contactor
Coil?
NO
Repair Wiring
Replace Time Delay Relay
No
10 Minute Time
Delay Expired?
NO
Wait 8 Minutes - Do Not Install
Compressor Time Delay Jumper
Yes
Power To Contactor Coil?
Yes
Install
Compressor Time
Delay Jumper
Yes