Manitowoc RFF Series - LOW PRESSURE CUTOUT (LPCO) CONTROL

Manitowoc RFF Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
86 Part Number 000015433_05 3/21
LOW PRESSURE CUTOUT (LPCO) CONTROL
Model Cut-Out Cut-In
UFF0200 / RNF0320
RNF0620 / RFF0620
RNF1100 / RFF1300
7 psig ±2
(.5 bar ±.2)
36 psig ±2
(2.5 bar ±.2)
RNF1020C / RFF1220C
RNF2000C / RFF2200C
Control is located in
remote condensing
unit
12 psig ±2
(.8 bar ±.2)
35 psig ±5
(2.4 bar ±.3)
RFF2500
12 psig ±2
(.8 bar ±.2)
Manual Reset
FAN CYCLE CONTROL
Model Cut-Out (Open) Cut-In (Close)
UFF0200 / UNF0200
UNF0300 / RNF0320
RFF0320 / UFF0350
RNF0620 / RFF0620
RNF1100 / RFF1300
RFF1300 / RFF2500
215 ±5
(14.8 bar ±.3)
232 ±5
(16 bar ±.3)
Remote condensing units do not have a fan cycle control.