Part Number STH042 7/15 111
4. Recovered refrigerant must come from a
contaminant-free system. To decide whether the
system is contaminant free, consider:
Type(s) of previous failure(s)
Whether the system was cleaned, evacuated and
recharged properly following failure(s)
Whether the system has been contaminated by
this failure
Compressor motor burnouts and improper past
service prevent refrigerant re-use.
Refer to “System Contamination Cleanup on
page 115 to test for contamination.
5. “Substitute or Alternative Refrigerant
Must use only Manitowoc-approved alternative
refrigerants.
Must follow Manitowoc-published conversion
procedures.