24 Part Number 000014797 Rev02 05/18
Electrical Requirements
Voltage
The maximum allowable voltage variation is ±10% of the
rated voltage on the ice machine model/serial number
plate at start-up (when the electrical load is highest).
Fuse/Circuit Breaker
A separate fuse/circuit breaker must be provided for each
ice machine.
Total Circuit Ampacity
The total circuit ampacity is used to help select the wire
size of the electrical supply.
The wire size (or gauge) is also dependent upon location,
materials used, length of run, etc., so it must be
determined by a qualified electrician.
Electrical Specifications
Air-cooled Ice Machine
NOTE: Model/serial plate information overrides all data
listed in this chart.
Ice Machine
Voltage Phase
Cycle
Max. Fuse/
Circuit Breaker
Total Amps
U0140
UF0140
115/1/60 15 5.0
208-230/1/60 15 2.5
230/1/50 15 2.5
U0190/UF0190
115/1/60 15 6.0
208-230/1/60 15 3.0
230/1/50 15 2.5
U0240
UF0240
115/1/60 15 7.0
208-230/1/60 15 3.5
230/1/50 15 4.0
U0310
UF0310
115/1/60 15 10.0
208-230/1/60 15 4.5
230/1/50 15 4.5
NOTE: Model/serial plate information overrides all data listed in
this chart.