Key capabilities including testing, factory programming, remote reset, trip-point repeatability, and environmental resistance.
Details normal operation, trip conditions, latching, and the procedure for resetting the vibration switch.
Explains the typical two-wire control circuit connection for the IMI 686B vibration switch with an ABB VFD.
Illustrates wiring for the Marley IB1 interface box for alarm and control with the vibration switch.
Specifies the available voltage ratings for the vibration switch.
Explains sensor type, factory programming, contact config, and reset method for the vibration switch.
Covers mounting stud, typical locations, and explosion-proof design availability.
Addresses cable length, lead extension, and conduit requirements for the vibration switch.
Details interfacing the switch with Marley AIO panels and electromechanical motor starters.
The IMI 686B vibration switch is a specialized device designed for cooling tower applications, offering robust vibration protection for mechanical equipment. Its primary function is to monitor vibration levels and trigger a shutdown if continuous high vibration is detected, preventing potential damage to the cooling tower's components.
The IMI 686B operates as a normally closed (N.C.) switch. In its normal state, with or without power, the switch is closed, allowing mechanical equipment to operate. Once powered, it remains closed. If the switch detects a continuous high vibration level for 3 seconds or more, it will open and latch in an open state. This 3-second delay is crucial for preventing nuisance tripping during startup or momentary vibration spikes, allowing the fan to accelerate through critical frequencies. When tripped, the cooling tower has experienced abnormal vibration and requires inspection before being returned to service. To reset the switch after a vibration event, power must be discharged and then reapplied. This can typically be achieved by cycling power at the VFD (Variable Frequency Drive) or motor starter line side disconnect. For VFDs, it's essential to keep power off for 30 seconds to allow capacitors to fully discharge. The switch is factory-programmed by SPX specifically for cooling tower vibration protection, and reprogramming is generally not recommended unless directed by SPX.
In summary, the IMI 686B vibration switch is a robust, reliable, and specialized solution for protecting cooling tower mechanical equipment from excessive vibration, offering advanced features like remote reset, intelligent tripping delays, and a durable, maintenance-free design.