WHAT TO DO IF THE ALARM SOUNDS
1. Alert any small children and elderly persons
2. Leave immediately by your plan of escape. Every second counts, so don’t waste time getting
dressed or picking up valuables.
3. In leaving, don’t open any inside door without rst feeling its surface. If hot, or if you see smoke
seeping through cracks, don’t open that door! Instead, use your alternate exit. If inside door is cool,
place your shoulder against it, open it slightly and be ready to slam it shut if heat and smoke
rush in.
4. Stay close to the oor if air is smoky. Breathe shallowly through a wet cloth if possible.
5. Once outside, go to your selected meeting place and make sure everyone is there.
6. Call the Fire Brigade on 000.
7. Don’t return to your home until ofcials say that it is safe to do so. For further information on re
safety contact your local Fire Brigade.
INSTALLATION
All electrical installations must be carried out by a qualied electrician, in accordance
with Australian Standards.
1. Once the power has been connected and the battery has been tted, the smoke alarm is
operational.
2. When smoke is detected, the alarm will sound a loud audible alarm, and the red LED will ash. The
audible alarm will cease once the level of smoke is reduced.
3. In standby mode, the red LED will ash periodically to indicate that the alarm is operating correctly.
4. The green LED glows when the alarm is connected to main power. This should always be on.
5. The smoke alarm will function correctly as a stand alone alarm, or interconnected with other
FSA-25000 alarms
6. When powering up the unit several audible beeps may sound, this is normal operation.
7. All interconnected alarms must be supplied from a single power circuit.
8. Do not connect the interconnect wire to active or neutral.
9. Connect and power the alarm with 220-240VAC only. The smoke alarm is suitable for use with
non-pure sinusoidal power sources (eg power derived from square-wave inverters.)
10. All wiring must comply with AS3100 wiring rules.
Stripping length
10mm
Use minimum of 1mm
2
250V insulated wire
for all wiring including inter-connecting.
50mm
Inter-connected 1mm
2
Neutral
Live/Active
Black
Red
230-240V a.c.
1mm
2
minimum
150 meters maximum between rst and last
interconnected smoke alarm
Close this ap after wiring.
TESTING
Test the smoke alarm weekly to conrm normal operation
1. Test alarm, by pressing the Test button for 3 seconds, until the alarm sounds.