Hydronic Highwall
22 Installation
it out after finish piping.
Push the lower part of the Indoor Unit up to the wall, and then move the Indoor Unit from side to side, up
and down to check if it is hooked securely.
13.5 Water pipe installation
Connection of the water pipe should be done by professionals. Double-span should be used when connecting
pipes of Indoor Unit.
At the first debugging, completely expel air from coils via expelling valve.
13.6 Wiring chart
The wiring diagram please refers to chapter 8.
Cautions:
The reserved function is indicated in broken line table, users can select it when necessary.
An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual
current device (RCD) with the rating of above 10mA shall be incorporated in the fixed wiring according
to the national rule.
The appliance shall be installed in accordance with national wiring regulations.
Take out the faceplate, and then dismantle the display cover
Individual connect the power cord and signal line, adjust the dial switch.