Hydronic Highwall
Specifications 5
6. Specifications
H/M/L m
3
/h 425/360/320 680/580/510
H/M/L CFM 250/210/190 400/340/300
Capacity H/M/L kW 2.63/2.41/2.16 3.28/2.83/2.41
Water flow rate H l/h 452 564
Water pressure drop H kPa 29.4 43.5
Capacity H/M/L kW 3.36/3.1/2.79 4.37/3.73/3.17
Water pressure drop H kPa 27.3 40.8
level H/M/L dB(A) 30/24/20 37/31/26
Type Low noise 4-speed fan motor
Quantity 1
Type Cross-flow fan
Quantity 1
Row 2
Max. Working pressure Mpa 1.6
Diameter mm Φ7
Dimensions W×H×D mm 915×230×290
Net weight kg 13 13.3
Packing W×H×D mm 1020×315×390
Gross weight kg 16.3 16.7
Water inlet/outlet pipe Inch G3/4"
Drain pipe mm ODΦ20
R51/E (standard)
Note:
1. H: high speed; M: medium speed; L: low speed
2. Cooling Conditions: entering water 7°C, temperature rise 5°C, entering air temperature 27°C DB,19°CWB.
Heating Conditions: entering water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise is tested in semi-anechoic test room.