EasyManua.ls Logo

MAXTHERMO MC-2838 - Error Information

Default Icon
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
Display Code
Description
ln1E Open circuit of main control sensor
* AdCF A/D convector failed.
* CJCE Cold junction compensation failed.
ln2E Open circuit of sub control sensor.
uuu1 PV exceeds USPL
nnn1 PV under LSPL
uuu2 Input signal of sub control exceeds the upper limit.
nnn2 Input signal of sub control under the upper limit.
* rAmF RAM failed.
lntF Interface failed.
AutF Auto tuning failed.
NOTE: If the “*marked error occurs, the Temperature Controller need repair.
Please send it to the nearest sales office or retail dealer.
Error information:
Error information:
Type Code Range
S S 0~1600
B b 0~1800
R r 0~1700
k1 0.0~400.0
K
k2 0~1300
E1 0.0~300.0
E
E2 0~600
T t 0.0~400.0
J1 0.0~400.0
J
J2 0~800
WU3-RE25 w 0~2000
n n 0~1300
Pt1 -199.9~199.9
PT
Pt2 -200~800
CU50 CU50 -50.0~150.0
AN1 An1 0~20MV/-1999~9999
AN2 An2 0~50MV/-1999~9999
AN3 An3 0~5V/-1999~9999
AN4 An4 4~20MA/-1999~9999
Input
Input
selection table:
selection table:
P.11

Related product manuals