INSTALLATION INSTRUCTIONS
1. Inspect the air conditioner and verify correct functionality before mounting the air conditioner. See
HANDLING AND TESTING THE AIR CONDITIONER on page 3.
2. Determine if the unit is to be surface or recess mounted. Using the appropriate cutout dimensions,
see Mounting Cutout Dimensions on page 5 of this manual, prepare the enclosure opening for either
surface or recess mounting.
3. Using the gasket kit provided, install gaskets to air conditioner.
4. Mount air conditioner on enclosure using mounting bolts and screws provided. “EZ” mount tabs
can be used to hold unit on enclosure while mounting in place. Allow unit to remain upright for a
minimum of ve (5) minutes before starting. Caution! Air conditioner must be in upright position
during operation.
5. When routing the drain tube, caution should be taken to keep it from kinking or being elevated above
the exit point of the air conditioner. The drain tube must be on a continuous downward slope. A
slight elevation of the tube could result in secondary trap. FAILURE TO FOLLOW THESE INSTRUCTIONS
COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN.
6. Refer to top of nameplate for electrical requirements. Connect the power cord to a properly grounded
power supply. Use of an extension cord is not recommended. Electrical circuit should be fused with
slow blow or HACR circuit breaker.
Design Data
Model Voltage Hz
Full Load
Amps
Phase
BTU/Hr. @
Max Ambient
Temperature
Max Ambient
Temperature
(°F/°C)
Shipping
Weight
(lb./kg)
T200216GXXX 115 50/60 7.0 1 1800/2000 131/55 56/25
T200226GXXX 100 50/60 3.5 1 1800/2000 125/52 56/25
-XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specic model numbers.
Dimensional Drawing
1/4-20 Mounting Holes (12)
(6 on back face - 6 behind front cover)
Enclosure
Air Out
Ambient
Air In
Enclosure
Air In
Ambient Air
Out
Removeable
Hanging
Tabs (2)
.5 inch (13 mm) Drain Stub
FRONT
SIDE
BOTTOM
BACK
Mounting hardware for fully recessed
mounting is behind removable front cover.
Cleanable, reusable aluminum inlet lter slides
out slot in bottom of front cover.
Power Cord
Entrance
Thermostat
Adjustment
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com