Installation, Operation and Maintenance Manual
IOMM ACZ1
Group:
Chiller
Part Number
: 330262002
Effective:
December 2001
Supersedes:
New
Air-Cooled Scroll Condensing Units
ACZ 010A – ACZ 039A
10 to 43 Tons, 35 to 150 kW
R-22, 60 Hertz

Questions and Answers:

McQuay ACZ 028A Specifications

General IconGeneral
BrandMcQuay
ModelACZ 028A
CategoryHeat Pump
LanguageEnglish

Summary

Refrigerant Piping Guidelines

Suction Line Sizing and Routing

Guidelines for sizing and routing suction lines, including noise considerations.

Liquid Line Sizing and Operation

Liquid Line Requirements

Assuring proper liquid refrigerant flow to the expansion valve.

Control System Overview

Start-up and Shutdown Procedures

Step-by-step instructions for unit start-up and shutdown.

Unit Operation Details

Sequence of Operation

Describes the typical operational sequence of the unit.

Unit Protection and Alarms

Unit Shutdown Process

Details the sequence of events during a unit shutdown.

Electrical Data and Field Wiring

Field Wiring Requirements

Covers compliance with codes and wire requirements for field connections.

Table 5: Electrical Data (Single Point)

Details electrical data and wiring for single-point power connections.

Electrical Data: Amp Draw

Table 6: Compressor and Fan Motor Amp Draw

Lists rated and locked rotor amp draw for compressors and fans.

Electrical Data: Field Wiring

Table 7: Field Wiring Data (Single Point Power)

Provides field wiring data for single-point power connections.

Electrical Wiring Diagram

Typical Field Wiring Diagram

Illustrates the typical electrical connections for field wiring.

System Maintenance Procedures

Refrigerant Sightglass Observation

How to interpret the sightglass for refrigerant charge and moisture.

MicroTech II Controller Operation

Compressor Motor Protection

Details the solid-state motor protection for compressors.

FanTrol Head Pressure Control

Explains the fan control method for maintaining head pressure.

MicroTech II Controller Setpoints and Alarms

Table 10: Detailed Setpoints

Lists various configurable setpoints with default and range values.

Equipment Protection Alarms

Defines equipment protection alarms, conditions, and actions.

MicroTech II Controller Alarms and Unit Enable

Shutdown and Limit Alarms

Details shutdown and limit alarms, their causes, actions, and reset.

MicroTech II Controller Modes and Ambient Control

Low Ambient Start Sequence and Limits

Procedure for low ambient start sequence and automatic limit adjustments.

Using the MicroTech II Controller Interface

Menu Navigation Methods

Explains how to navigate through the controller's menu matrix.

MicroTech II Controller Menu Navigation

Changing Setpoint Values

Detailed steps for modifying setpoint values using the keypad.

MicroTech II Controller Menu Structure

Figure 12: Menu Matrix Overview

Visual representation of the controller's menu hierarchy.

MicroTech II Controller Alarm and Set Screen Definitions

Alarm Screen Definitions

Explains how active and logged alarms are displayed and cleared.

Set Screen Definitions

Guides on how to change setpoint values for various parameters.

MicroTech II Controller Setpoint Configuration (Part 2)

Compressor Anti-Recycle Timers

Configuring minimum run and stop times for compressors.

MicroTech II Controller Alarm Limits

Service and Component Maintenance

Optional Controls and Hot Gas Bypass

Hot Gas Bypass System Details

Troubleshooting Guide

Troubleshooting Chart and Corrective Steps

A comprehensive chart listing common problems and their solutions.