9
4. 1
st
Stage Temperature Differential
(1°F to 3°F) (0.5°C to 1.5°C)
Set the number of degrees between your “setpoint” temperature
and your “turn on” temperature.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
5. 2
nd
Stage Temperature Differential
(1°F to 6°F) (0.5°C to 3.0°C)
Set the number of degrees between when stage 1 turns on
and when stage 2 turns on.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
6. Minimum Deadband
(2°F to 9°F) (1.0°C to 4.5°C)
Set the minimum separation between heat setpoint and
cool setpoint in Auto Changeover Mode.
Press the or button to set deadband.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
7. Staged Off Outputs
Select whether the outputs for heating and cooling are staged
off independently or are satisfied simultaneously.
1 = outputs staged off independently
0 = outputs off simultaneously
Press the or button to set deadband.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
8. Minimum Cool Setpoint
(45°F to 75°F) (7°C to 24.0°C)
Adjust to control the minimum Cool set temperature allowed.
Press the or button to select.
Press the
SW6 button
to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE