19
Application Information M5MSY_(i)
* The fi gures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation and
conductors used.
** The appropriate voltage range should be checked with label data on the unit.
Model M5WMY10 LR M5WMY15 LR
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size* mm
2
Number of core
3.0
3
3.0
3
Interconnection cable size* mm
2
Number of core
1.5
4
1.5
4
Recommended time delay fuse* A 25 25
Model M5WMY10/15 JR M5WMY20 JR
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size* mm
2
Number of core
3.0
3
3.0
3
Interconnection cable size* mm
2
Number of core
1.5
4
2.5
4
Recommended time delay fuse* A 25 25
Model M5CKY10 C/CR M5CKY15 C/CR M5CKY20 C/CR
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size* mm
2
Number of conductors
3.0
3
3.0
3
3.0
3
Interconnection cable size* mm
2
Number of conductors
1.5
4
1.5
4
2.5
4
Recommended time delay fuse* A 25 25 25
Model M5CCY10 C/CR M5CCY15 C/CR M5CCY20 C/CR
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size* mm
2
Number of conductors
3.0
3
3.0
3
3.0
3
Interconnection cable size* mm
2
Number of conductors
1.5
4
1.5
4
2.5
4
Recommended time delay fuse* A 25 25 25
Model M5CMY15 E/ER M5CMY20 E/ER
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size* mm
2
Number of conductors
3.0
3
3.0
3
Interconnection cable size* mm
2
Number of conductors
1.5
4
2.5
4
Recommended time delay fuse* A 25 25