EasyManuals Logo

McQuay MCK Service Guide Book

McQuay MCK
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
45
Ducted Blower B/D/ER Series Model Multi Compressors
Rooftop Packaged Air Conditioner Multi Compressors
Model Board Handset
SB 150B2/BR2 – 600B4/BR4 SQ2.0 SQ-LCD
SB 125D2 – 500D4 SQ2.0 SQ-LCD
SB 125ER2 – 600ER4 SQ2.0 SQ-LCD
RT 150 – 420A/AR SQ2.0 SQ-LCD
Error Code
When the system is on and an error occurs, the ON/OFF LED on the LCD panel will blink and an error
code is shown. When the system is off and there is a thermistor error, the ON/OFF LED is off but the error
code is still displayed. Each error code represents different message as below:
Error
Code
Faulty Indication
Error
Code
Faulty Indication
E01 Require manual reset (possible causes) E19 Indoor coil sensor 4 short
E02
Compressor 1 high temperature
(overload)
E20 Indoor coil sensor 1 open
E03
Compressor 2 high temperature
(overload)
E21 Indoor coil sensor 2 open
E04
Compressor 3 high temperature
(overload)
E22 Indoor coil sensor 3 open
E05
Compressor 4 high temperature
(overload)
E23 Indoor coil sensor 4 open
E06
Compressor 1 high pressure trip /
contact open
E24 Outdoor coil sensor 1 short
E07
Compressor 2 high pressure trip /
contact open
E25 Outdoor coil sensor 2 short
E08
Compressor 3 high pressure trip /
contact open
E26 Outdoor coil sensor 3 short
E09
Compressor 4 high pressure trip /
contact open
E27 Outdoor coil sensor 4 short
E10
Compressor 1 trip / low refrigerant /
outdoor abnormal
E28 Outdoor coil sensor 1 open
E11
Compressor 2 trip / low refrigerant /
outdoor abnormal
E29 Outdoor coil sensor 2 open
E12
Compressor 3 trip / low refrigerant /
outdoor abnormal
E30 Outdoor coil sensor 3 open
E13
Compressor 4 trip / low refrigerant /
outdoor abnormal
E31 Outdoor coil sensor 4 open
E14 Room sensor short E32 Compressor 1 de-ice
E15 Room sensor open E33 Compressor 2 de-ice
E16 Indoor coil sensor 1 short E34 Compressor 3 de-ice
E17 Indoor coil sensor 2 short E35 Compressor 4 de-ice
E18 Indoor coil sensor 3 short