EasyManuals Logo

McQuay MQC164036CCK216B User Manual

McQuay MQC164036CCK216B
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
50
E5: Outdoor unit failure
Check the detail of failure at the outdoor unit.
E7: EEPROM failure
Change the indoor mainboard
E8: The protection for the stall of indoor fan motor
Solution:
(1)Check the connection between motor and main board is loosen or not, inset it firmly
(2)Check that is something blocked the motor or fan blade, if it is, remove it; if not, change the indoor main board or
DC motor
E9: Indoor unit and wire controller communication failure
Solution:
(1)Check the connection between wired controller and main board is loosen or not, inset it firmly
(2)Connect with a new wired controller, if not solve, change with a new communication cable
(3)If all above steps done, it still not solves, change the indoor main board or transformer.
F6: Outdoor condenser pipe temperature sensor (T3) failure
Solution:
(1)Check the T3 sensor connection loosen or not, inset it firmly, if not solve, go to next step;
(2)Take out the sensor, measure the resistance of the sensor, it is about 5KΩ at 25, if not, replace it; if resistance
normally, change the main board.
EE: Water fulfilled protection (Alarm of condensing water overflow)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MQC164036CCK216B and is the answer not in the manual?

McQuay MQC164036CCK216B Specifications

General IconGeneral
BrandMcQuay
ModelMQC164036CCK216B
CategoryFan
LanguageEnglish

Related product manuals