43
Wall Mounted Split Type
Note :
a. PRESSURE DROP CORRECTION FACTOR = 1.2947 - 0.0021 * ( EWT°C * 1.8 + 32 )
b. PRESSURE DROP CORRECTION FACTOR = 1.2947 - 0.0021 * EWT°F
Water Flow Vs Pressure Drop
LITRES/M USGPM kPa PSI
4.00 1.06 20.23 2.93
5.33 1.41 27.04 3.92
6.66 1.76 33.88 4.91
7.99 2.11 40.75 5.91
9.32 2.46 47.65 6.91
4.79 1.27 26.96 3.91
6.39 1.69 36.00 5.22
7.99 2.11 45.06 6.54
9.59 2.53 54.15 7.85
11.19 2.96 63.26 9.18
5.50 1.45 33.20 4.82
7.33 1.94 44.27 6.42
9.16 2.42 55.34 8.03
10.99 2.90 66.41 9.63
12.82 3.39 77.47 11.24
7.79 2.06 17.71 2.57
10.38 2.74 24.09 3.49
12.98 3.43 30.71 4.45
15.58 4.11 37.56 5.45
18.17 4.80 44.65 6.48
9.08 2.40 19.88 2.88
12.11 3.20 26.91 3.90
15.14 4.00 34.13 4.95
18.17 4.80 41.56 6.03
21.20 5.60 49.20 7.14
11.13 2.94 26.21 3.80
14.84 3.92 34.90 5.06
18.55 4.90 43.66 6.33
22.26 5.88 52.51 7.62
25.97 6.86 61.44 8.91
MODELS
FLOW RATE WATER PRESSURE DROP
MWM007G2W
MWM301W
MWM010G2W
MWM015G2W
MWM020G2W
MWM025G2W

Other manuals for McQuay MWM-G2W