EasyManuals Logo

McQuay WGS190AW User Manual

McQuay WGS190AW
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
26 WGS 130A to 190A OM WGS-5
Figure 7, Evaporator Pressure Drop WGS 130 – WGS 190
100 200 300 400 500 600 700
800
900
1000
2000
Flow Rate (GPM)
Pressure Drop (ft of water)
Flow Rate (L/s)
6131925323844505763
126
12
18
24
27
30
9
21
15
60
90
120
150
180
Pressure Drop (kPa)
3
4
5
6
7
8
9
10
20
30
40
50
60
WGS 160, 170, 190
WGS 130, 140
Minimum Flow Nominal Flow Maximum Flow
Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop
WGS Model
gpm L/s Ft. kPa gpm L/s Ft. kPa gpm L/s Ft. kPa
130AW/AA
195 12.3 5.8 17.4 312 19.7 13.5 40.4 520 32.9 33.9 101.1
140AW/AA
211 13.4 6.7 20.0 338 21.4 15.6 46.6 563 35.6 39.0 116.5
160AW/AA
235 14.9 4.6 13.8 376 23.8 10.8 32.3 627 39.7 27.3 81.6
170AW/AA
254 16.1 5.3 15.9 407 25.8 12.5 37.3 678 42.9 31.6 94.2
190AW/AA
273 17.3 6.1 18.1 437 27.7 14.2 42.5 728 46.1 35.9 107.2
Note: Minimum, nominal, and maximum flows are at a 16F, 10F, and 6F chilled water temperature range respectively and at ARI tons.