OM WGS-5 WGS 130A to 190A 33
Description Default Range PW
EXV
EXV control Auto Auto, manual M
Manual EXV position 0 0-6386 M
Service Pumpdown No No,Yes M
Preopen Timer (water cooled only) 20 20 to 120 seconds M
Sensors (NOTE 1)
Evap pressure offset 0 -10.0 to 10.0 psi M
Cond pressure offset 0 -10.0 to 10.0 psi M
Suction temp offset 0 -5.0 to 5.0 deg M
Discharge temp offset 0 -5.0 to 5.0 deg M
Slide Minimum Position Offset 0 -15 to 15% M
Slide Maximum Position Offset 0 -15 to 15% M
Fans (available for air-cooled only)
Fan VFD enable On Off, On M
Number of fans 4 4 to 6 M
Saturated Condenser Temp Target Min 90.0 80.0-110.0
o
F M
Saturated Condenser Temp Target Max 110.0 90.0-120.0
o
F M
Stage 1 On Deadband 8.0 1.0-20.0
o
F M
Stage 2 On Deadband 10.0 1.0-20.0
o
F M
Stage 3 On Deadband 11.0 1.0-20.0
o
F M
Stage 4 On Deadband 12.0 1.0-20.0
o
F M
Stage 2 Off Deadband 20.0 1.0-25.0
o
F M
Stage 3 Off Deadband 16.0 1.0-25.0
o
F M
Stage 4 Off Deadband 11.0 1.0-25.0
o
F M
Stage 5 Off Deadband 8.0 1.0-25.0
o
F M
VFD Max Speed 100% 90 to 110% M
VFD Min Speed 25% 20 to 60% M
Forced Fantrol 1 2 1 to 4 M
Forced Fantrol 2 3 1 to 4 M
Forced Fantrol 3 4 1 to 4 M
Notes:
1. Offsets are used to fine-tune certain readings generated by sensors. For example, if the controller was
showing a 125 psi value and a calibrated pressure gauge at the same location showed 127 psi, an offset of
+2 psi would be entered and the controller would then read the corrected value of 127 psi.
Table 15, RLA/FLA Values
Compressor 575V 460V 380V 230V 208V 400V (50Hz)
RLA
197
113 141 178 282 312 141
179
94 122 145 240 267 122
167
85 112 128 210 232 112
FLA
All
113 141 178 282 312 141
NOTE: Table values used for circuit controller input.