OM WGS-5 WGS 130A to 190A 81
Water-cooled: Air-cooled:
SET UNIT SPs (12) SET UNIT SPs (12)
Sensor Offset Sensor Offset
Cond EWT= XX.XF OAT= XX.XF
Cond LWT= XX.XF
SET UNIT SPs (13)
CLOCK
mm/dd/yyyy
hh:mm day
SET UNIT SPs (14)
Units = F/psi
Lang = ENGLISH
After entering a valid manager password, selecting F/psi will provide IP units; selecting
C/kPa will provide SI units.
SET UNIT SPs (15)
Protocol=
Ident Number=
Baud Rate=
SET UNIT SPs (16)
Enter Password:0000
Active Password
Level:none
Compressor Set Points
SET COMP SPs (1)
Seq # Comp 1= X
Seq # Comp 2= X
SET COMP SPs (2)
Max Comps On = x
Start-Start =XX min
Stop-Start =XX min
This menu sets the anti-recycle timers. Stop-Start is the time required before starting a
compressor after it has stopped. Start-Start is the time required before starting a compressor
after the last time it has started. It is recommended that the default values of 5 minutes and
15 minutes not be changed. Max Comps On can be 1 or 2 with 2 being the default.