-21 -
4. Technician settings (cont’)
P11 – Window contact delay time
Range: 0…999 seconds
Default: 600 seconds
P12 – Door switch / Door key-tag (terminals T1,0) polarity
“00” - Normally open (default)
“01” - Normally close
P13 – Door switch / Door key-tag delay time
Range: 0…999 seconds
Default: 180 seconds
P14 – Enable/Disable Auto change over mode
“00” - Disable Auto change over mode
“01” - Enable Auto change over mode (default)
P15 – Occupancy sensor logic (PIR)
“00” - Thermostat turns off when unoccupied
and back on when re-occupied
“01” - Thermostat turns off when unoccupied
and remains off when re-occupied
“02” - Thermostat uses economy set points (default)
P16 – Enable/Disable Occupancy sensor
“00” - Disable
“01” - Enable (default)