29
USER´S MANUAL
ALARMS Alarms Menu
ALRM.SET Alarm Setup (Enable/Disable)
AUTO Automatic search of C/K response value
AUTO.SET Automatic Setup Sequence
BANK.PRE Bank Pre-configuration Sequence Menu
BANK.TST Bank Test: each step is automatically connected
and disconnected in turn. This facilitates testing of
the operation of each capacitor step contactor.
See also Step Test.
CIRC.A Circular A stepping program
CIRC.B Circular B stepping program
C/K Response value, normally set up automatically by
the controller
CLR.STAT Clear Statistics
COMMISS Commissioning Sequence Menu
COS PHI Target cos
value 0,8ind 1.00 0,9cap
CT Current Transformer primary setting, xxx/5 A 25/5 % 6000/5
DELAY Safety Delay or reconnection delay. Response 10s 50s 600s
delay is fixed 20% of reconnection delay. The
default value corresponds to capacitors with
internal discharge resistors 50V 1 min
ENGLISH Language names: English, for instance
ERR NN Error in parameter search or verify. NN= error number
FACTOR.S Restore Factory Settings
IGNORED The controller does not require the information
about step sequence for any program outside
Optimal. The controller defines it automatically.
I HIGH Current too high >115%
I
N
I LOW Current too low <2,5%
I
N
LANGUAG Language Selection for menus
LL Line to Line connection
LN Line to Neutral connection
LV Low Voltage
MAINTEN Maintenance Menu
MAN.SET Manual Setup Sequence Menu
MANUAL Manual setting of C/K response value. See further 0,01 0,50 1,99
MEASURE Measurements Menu
7. Glossary
Display
information
Long form text Min
value
Default
value
Max
value