MI 3200 TeraOhm 10 kV Specifications
44
Display range Test voltage (V) Resolution Accuracy
0 9999 V
1 V
(3 % of reading + 3 V)
10 kV
0.1 kV
(3 % of reading)
Withstanding voltage DC
DC test voltage:
Voltage value: Any value within 500V and 10kV.
Accuracy: -0 / +10 % + 20 V.
Display range Test voltage (V) Resolution Accuracy
0 9999 V
1 V
(3 % of reading + 3 V)
10 kV
0.1 kV
(3 % of reading)
Leakage current
Display range Itrigg (mA) Resolution Accuracy
0.000 0.009 1
A
(3 % of reading + 3 digits)
0.01 5.50 10
A
(3 % of reading)
Voltage
Voltage AC or DC
Display range External Voltage (V) Resolution Accuracy
0 600
1 V
(3 % of reading + 4 V)
Frequency of external voltage
Display range (Hz) Resolution Accuracy
0 and 45 65
0.1 Hz
0.2 Hz
Note:
- for frequency between 0 and 45 Hz displayed <45 Hz
- for frequency over 65 Hz displayed >65 Hz
Input resistance: 3 M 10 %
Capacitance
Measuring range C: 50 F*
Display range C Resolution Accuracy
0.0 99.9 nF
0.1 nF
(5 % of reading + 2 digits)
100 999 nF
1 nF
1.00 50.00 F
10 nF
*Full-scale value of capacitance is defined according to the following equation:
C
FS
= 10 F * U
test
[kV]