EasyManuals Logo

METRON MP430 Series User Manual

METRON MP430 Series
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
Page 16 of 25
Printing Configuration Setpoints: The following applies if a printer has been installed or a PC is connected to the RS232 com
port using a null modem cable. When the [PRINT] button is pressed while looking at a configuration setpoint screen, a menu for
what is to be printed is displayed. Pressing [1] prints just the set point screen currently being displayed. Pressing [2] prints all the
set points in the section of set points currently displayed. Pressing [3] prints all the set point screens of all five set point sections.
NOTE: when printing all set points, only Aux#01 User Programs 501 through 515 will be printed. To print any of the remaining
eleven aux alarm settings, press [PRINT] when inside the appropriate Aux alarm and select [2] for “2) PRINT 500 SETPTS.”
The 501 through 515 Aux User Programs for that aux alarm will be printed.
101 SYSTEM SETPOINTS
Pump Start
Pressure
[ 60] psi 0-999
PRINT OPTIONS
1) PRINT THIS SETPT
2) PRINT 100 SETPTS
3) PRINT ALL SETPTS
Typical Configuration Setpoint
Printout
101 SYSTEM SETPOINTS
Pump Start
Pressure
[ 60] psi 0-999
102 SYSTEM SETPOINTS
Pump Stop
Pressure
[ 90] psi 0-999
103 SYSTEM SETPOINTS
Pump Start Delay
Time
[ 10] seconds 0-999
509 AUX USER PROGRAMS
Aux Alarm #01
2nd Control Output
[ 0] 12-25
510 AUX USER PROGRAMS
Aux Alarm #01
3rd Control Output
[ 0] 12-25