EasyManua.ls Logo

Micom P341 - Page 25

Default Icon
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Update Documentation P341/EN AD/F43
MiCOM P341
(AD) -21
Non-Directional
Directional Fwd
Directional Rev
IN1>3 Current Set: 0.08…32.00 In
IN1>3 Time Delay: 0.00…200.00s
IN1>4 as IN>3
IN1> Blocking:
Binary function link string, selecting which
ground overcurrent elements (stages 1 to 4)
will be blocked if VTS detection of fuse
failure occurs.
IN1> Char Angle: -95… +95
o
IN1> Polarization:
Zero Sequence
Neg. Sequence
IN1> VNpol Set:
0.5…80.0V (100/110V)
2…320V (380/480V)
IN1> V2pol Set:
0.5…25.0V (100/110V)
2…100V (380/480V)
IN1> I2pol Set: 0.08…1.00 In
The IDG curve is commonly used for time
delayed earth fault protection in the Swedish
market. This curve is available in stage 1 of
the Earth Fault protection.
The IDG curve is represented by the following
equation:
t = 5.8 - 1.35 log
e
N > Setting
in seconds
Where:
= Measured current
N>Setting = An adjustable setting which
defines the start point of the
characteristic
Although the start point of the characteristic is
defined by the “N>” setting, the actual relay
current threshold is a different setting called
“IDG s”. The “IDG s” setting is set as a
multiple of “N>”.
An additional setting “IDG Time” is also used
to set the minimum operating time at high
levels of fault current.
0
1
2
3
4
5
6
7
8
9
10
110100
I/IN>
Operating time (seconds)
IDG Is Setting Range
IDG Time Setting Range
P2242ENa
IDG Characteristic
SEF/REF Prot’n
SEF/REF Options:
SEF
SEF Cos (PHI)
SEF Sin (PHI)
Wattmetric
Hi Z REF
ISEF>1 Function:
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
RI
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
IDG
ISEF>1 Directional:
Non-Directional
Directional Fwd
Directional Rev.
ISEF>1 Current Set: 0.005...0.10 In
ISEF>1 IDG Is: 1.0...4.0 In
ISEF>1 Time Delay: 0.00...200.00s
ISEF>1 TMS: 0.025...1.200
ISEF>1 Time Dial: 0.01...100.0
ISEF>1 IDG Time: 1.00...2.00
ISEF>1 Reset Char: DT/Inverse
ISEF>1 tRESET: 0.00...100.00s
ISEF>2 as ISEF>2
ISEF>3 Status:
Disabled
Enabled
ISEF>3 Directional:
Non-Directional
Directional Fwd
Directional Rev
ISEF>3 Current Set: 0.005...0.80 In
ISEF>3 Time Delay: 0.00...200.00s
ISEF>4 as ISEF>3
ISEF> Blocking:
Binary function link string, selecting which
ground overcurrent elements (stages 1 to 4)
will be blocked if VTS detection of fuse
failure occurs.
ISEF> Char. Angle: -95...+95 o
ISEF> VNpol Set:
0.5...80.0V (100/120V)
2...320V (380/480V)
WATTMETRIC SEF:
PN> Setting: 0....20In W (100/120V)
PN> Setting: 0 ....80In W (380/480V)

Related product manuals