EasyManua.ls Logo

Micom P341 - Current Loop Output

Default Icon
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P341/EN AD/F43 Update Documentation
(AD) -24
MiCOM P341
CLI1 Minimum: -9999…+9999
CLI1 Maximum: -9999…+9999
CLI1 Alarm: Disabled/Enabled
CLI1 Alarm Fn: Over/Under
CLI1 Alarm Set: CLI1 min…CLI1 max
CLI1 Alarm Delay: 0.0…100.0s
CLI1 Trip: Disabled/Enabled
CLI1 Trip Fn: Over/Under
CLI1 Trip Set: CLI1 min…CLI1 max
CLI1 Trip Delay: 0.0…100.0s
CLI1 I< Alarm (4…20 mA input only):
Disabled/Enabled
CLI1 I< Alm Set (4…20 mA input only):
0.0…4.0mA
CLI2/3/4 as CLI1
Current Loop Output
CLO1 Output 1: Disabled/Enabled
CLO1 Output Type:
0 - 1mA
0 - 10mA
0 - 20mA
4 - 20mA
CLO1 Set Values: Primary/Secondary
CLO1 Parameter: As shown below*
CLO1 Min: Range, step size and unit
corresponds to the selected parameter
CLO1 Max: Same as CLO1 Min
CLO2/3/4 as CLO1
Current Loop Output Parameters
Current Magnitude:
IA Magnitude
IB Magnitude
IC Magnitude
IN Derived Mag: 0.00…16.0
I Sen Mag: 0.00… 2.0A
Phase Sequence Components:
I1 Magnitude
I2 Magnitude
I0 Magnitude:
0.00…16.0A
Phase Currents:
IA RMS*
IB RMS*
IC RMS*
0.00…16.0A
P-P Voltage Magnitude:
VAB Magnitude
VBC Magnitude
VCA Magnitude
0.0…200.0V
P-N Voltage Magnitude:
VAN Magnitude
VBN Magnitude
VCN Magnitude
0.0…200.0V
Neutral Voltage Magnitude:
VN1 Measured Mag
VN Derived Mag
0.0…200.0V
Phase Sequence Voltage Components:
V1 Magnitude*
V2 Magnitude
V0 Magnitude
0.0…200.0V
RMS Phase Voltages:
VAN RMS*
VBN RMS*
VCN RMS*
0.0…200.0V
Frequency: 0.00…70.0Hz
3 Phase Watts*: -6000W…6000W
3 Phase Vars*: -6000Var…6000Var
3 Phase VA*: 0…6000VA
3Ph Power Factor*: -1…1
Single Phase Active Power:
A Phase Watts*:
B Phase Watts*:
C Phase Watts*:
-2000W…2000W
Single Phase Reactive Power:
A Phase Vars*:
B Phase Vars*:
C Phase Vars*
-2000Var…2000Var
Single Phase Apparent Power:
A Phase VA*:
B Phase VA*:
C Phase VA*
0…2000VA
Single Phase Power Factor:
Aph Power Factor*
BPh Power Factor*
CPh Power Factor*
-1…1
3 Phase Current Demands:
IA Fixed/Roll/Peak Demand*
IB Fixed/Roll/Peak Demand*
IC Fixed/Roll/Peak Demand*
0.00…16.0A
3ph Active Power Demands:
3Ph W Fix/Roll/Peak Demand*
-6000W…6000W
3ph Reactive Power Demands:
3Ph Vars Fix/Roll/Peak Dem*
-6000Var…6000Var
Thermal Overload: 0.00…200.0%
CL Input 1-4: -9999…9999.0
Note 1: Measurements marked with an
asterisk, the internal refresh rate is
nominally 1s, others are 0.5 power
system cycles or less.
Note 2: The polarity of Watts, Var and power
factor is affected by the measurements
Mode setting.
Note 3: These settings are for nominal 1A and
100/120V versions only. For other
versions they need to be multiplied
accordingly.

Related product manuals