Relay type: P341 …
Software
Version
Major Minor
Hardware
Suffix
Original Date
of Issue
S1
Compatibility
Technical
Documentation
Description of Changes
03
Cont.
E A Dec 2002
Correction to undervoltage stage 2 (V<2) setting range. The
setting range has been increased from 10-70V to 10-120V
(Vn=110/120V) so that it is the same as V<1
Correction to VT ratio scaling problem in the disturbance
recorder
Correction to value of derived neutral current shown on the
front panel default display.
Minor bug fixes
V2.00 or Later P341/EN T/B11