EasyManua.ls Logo

Micom P341 - Page 57

Default Icon
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Update Documentation P341/EN AD/F43
MiCOM P341
(AD) -53
Relay type: P341 …
Software
Version
Major Minor
Hardware
Suffix
Original Date
of Issue
Changes
S1
Compatibility
Technical
Documentation
Description of
A A June 2001
Not released to production
Sensitive reverse power added
Neutral voltage displacement threshold, VN>1/2, increased
from 50 to 80V (Vn=100/120V), 200 to 320 V (Vn=380/480V)
Earth fault polarizing voltage threshold, Vnpol, increased
from 22 to 88V (Vn=100/120V) and 88 to 352V
(Vn=380/480V)
cos phi and sin phi features added to SEF protection
Minor bug fixes
V2.01 or Later P341/EN T/B11
B A July 2001
Not released to production
Minor bug fix to background self check diagnostics
introduced in 04A
V2.01 or Later P341/EN T/B11
C A Dec 2001 Minor bug fixes V2.01 or Later P341/EN T/B11
D A Jan 2002
Resolved possible reboot caused by Disturbance Recorder
Minor bug fixes
V2.01 or Later P341/EN T/B11
E A Feb 2002
Resolved possible reboot caused by invalid MODBUS
requests
Minor bug fixes
V2.01 or Later P341/EN T/B11
04
F A Dec 2002
Enhanced DNP 3.0 Object 10 support for Pulse On/Close
control points
DNP 3.0 Object 10 included in Class 0 poll
DNP 3.0 support for season in time information
V2.01 or Later P341/EN T/B11