Update Documentation P341/EN AD/F43
MiCOM P341
(AD) -59
Relay type: P341 …
Software
Version
Major Minor
Hardware
Suffix
Original Date
of Issue
S1
Compatibility
Technical
Documentation
Des
cription of Changes
05
Cont.
G A/B August 2000
Control input sales added to non volatile memory
German language text updated
Power measurement limits added to prevent non zero values
with no current and voltage. Also power factor
measurements limited to +/-1
In the Commissioning Test menu the DDB status has been
made visible on the front panel display
Support for the Trip LED Status and Alarm Status added to
G26 data type for MODBUS register 30001
Correction to the CB trip/Close functionality via MODBUS so
that local/remote setting in the CB control menu is not
ignored
Correction to MODBUS auto event extraction which does not
work correctly
DNP 3.0 Object 12 “CROB” implementation is now compliant
for simple function points
DNP 3.0 object 10 added to class 0 poll
Correction to DNP 3.0 time sync operation so that it does not
modify the season bit in the time stamp
Correction to the manual reset user alarms so that the event
record shows the alarm turning off when a reset command
has been issued. Previously the “alarm off” event is
produced once the initiating signal is removed.
Correction to the fault recorder window for current based trips
so that it can terminate properly once the FAULT_REC_TRIG
signal (DDB 288) is reset. Previously it needed to wait for
Relay 3 to reset also before termination
V2.05 or Later P341/EN T/D22