Update Documentation P341/EN AD/F43
MiCOM P341
(AD) -67
Relay type: P341 …
Software
Version
Major Minor
Hardware
Suffix
Original Date
of Issue
S1
Compatibility
Technical
Documentation
Description of Changes
07
Cont.
B A/C Oct 2003
Correction to the CB trip/Close functionality via MODBUS so
that local/remote setting in the CB Control menu is not
ignored
Correction to MODBUS auto event extraction which does not
work correctly in versions 05 and 06 software
Extension of the control input functionality to support pulse
and latch operations in DNP 3.0
DNP 3.0 object 10 added to class 0 poll
Correction to DNP 3.0 time sync operation so that it does not
modify the season bit in the time stamp
Correction to the manual reset user alarms so that the event
record shows the alarm turning off only when a reset
command
Correction to the fault recorder window for current based trips
so that it can terminate properly once the FAULT_REC_TRIG
signal (DDB 288) is reset. Previously it needed to wait for
Relay 3 to reset also before termination
Resolved incorrect derived ‘IN’ value on front panel default
display
Minor bug fixes
V2.09 or Later P341/EN M/E33