Micro-Air, Inc. Page 17 EasyTouch 2.5 Operations Manual
Rev 1.0 8/27/14
Figure 13 – EasyTouch General Settings Menu Screens
Refer to Table 1 for a quick reference to the General Settings. Refer to the sections that follow for
further details on each setting.
Table 1 – General Settings Parameters
Inside Temperature Calibration
Reversed Fan Speed in Heat
Shaded Pole or
Split Capacitor
(Resets reminder & clears
hours only)
Set Point Temp Differential
Auto Fan Speed Temp Differential
Relative Humidity Set Point
2
Set by Jumper / DX
Override / CW Override
Inside Temp Sensor Selection
Auto / Display / Alt. Air
1
CAN Bus is an FX2 option only and is not currently supported by EasyTouch
2
Relative Humidity control is an FX2 CW option only.