10.4.11 Follow me (optional)
1) If the indoor PCB receives the signal which
results from pressing the FOLLOW ME button on remote controller, the buzzer will emit a sound and
this indicates the follow me function is initiated. But when the indoor PCB receives signal which sent
from remote controller every 3 minutes, the buzzer will not respond. When the unit is running with
follow me function, the PCB will control the unit according to the temperature from follow me signal,
and the temperature collection function of room temperature sensor will be shielded, but the error
detective function of room temperature sensor will be still valid.
2) When the follow me function is available,
the PCB will control the unit according to the room temperature from the remote controller and the
setting temperature.
3) The PCB will take action to the mode
change information from remote controller signal, but it will not affected by the setting temperature.
4) When the unit is running with follow me
function, if the PCB doesn’t receive any signal from remote controller for 7 minutes or pressing
FOLLOW ME button again, the follow me function will be turned off automatically, and the temperature
will control the unit according to the room temperature detected from its own room temperature sensor
and setting temperature.
10.4.13 Point check function
Press the LED DISPLAY or LED or MUTE button of the remote controller three times, and then press
the AIR DIRECTION or SWING button three times in ten seconds, the buzzer will keep ring for two
seconds. The air conditioner will enter into the information enquiry status. You can press the LED
DISPLAY or AIR DIRECTION button to check the next or front item’s information within 27 seconds.
When the AC enter the “information enquiry” status, it will display the code name in 2 seconds, the
details are as follows.
Enquiry information Displaying code Meaning
T1 T1 T1 temp.
T2 T2 T2 temp.
T3 T3 T3 temp.
T4 T4 T4 temp.
When the AC enter into the information enquiry status, it will display the code value in the next 25s
, the
details are as follows.
Enquiry
information
Display value Meaning Remark
T1,T2,T3,T4,
-14—70 -14—70 1. All the displaying temperature is actual
value.
2. All the temperature is °C no matter what
kind of remote controller is used.
3. If the actual value exceeds the range, it