DLFSAB and DLFLAB: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
34
DIAGNOSIS AND SOLUTION (CONT.)
Temperature Sensor Check
1. Disconnect the temperature sensor from the PCB.
2. Measure the sensor’s resistance value using a multi-meter.
3. Check the corresponding temperature sensor resistance value.
Fig. 19 — Temperature Sensor Check
NOTE: Figure 19 is for reference only. The actual condition and specific value may vary according to temperature.
Turn off all power supplies or disconnect all wires to avoid electric shock.
Operate after compressor and coil have returned to normal temperature in
case of injury.
WA RNING