Product Features
Page 31
1.6.3 Outdoor Fan Control
For on-off models, outdoor units just have one single fan
speed. The operation of outdoor fan is consistent with the
operation of compressor, except the following situations.
High temperature protection of evaporator
Defrosting
Current protection
1.6.4 Defrosting mode
The unit enters defrosting mode according to the
temperature difference between T2 and T1, as well as
the compressor runtime.
In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the “ ” symbol is displayed.
If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
Compressor current is over than I
defrost
and lasts for
7s
The defrosting time has reached the setting value.
T2≥2°C(3.6°F) after entering defrosting mode for 3
minutes.
After entering defrosting mode for 2 minutes,
check the value of T2. The minimum temperature
of T2 is marked as T2min. If T2-T2min≥2°C(3.6°F)
during the following 4 minutes, AC will exit
defrosting mode(if T2≤-15°C(5°F),considers it as
-15°C(5°F)).
1.6.5 Evaporator Temperature Protection
When the evaporator temperature exceeds a preset
protection value, the compressor stops.
1.7 Auto-mode
This mode can be selected with the remote controller.
In auto mode, the machine selects cooling, heating, or
fan-only mode on the basis of T (T =T1-Ts).
∆T Running mode
∆T>2 Cooling
-3≤∆T≤2 Fan-only
∆T<-3 Heating*
Heating*: In auto mode, cooling only models run the fan
AC will run in auto mode in the below cases:
Pressing the forced auto button.
If AC is off, it will run in auto mode when the timer
on function is active.
After setting the mode, AC will run in auto mode if
the compressor keeps not running for certain time.
1.8 Drying mode
The compressor is cycled running with 10 minutes
on and then 5 minutes off. The indoor fan will keep
running at low speed.
In drying mode, if room temperature is lower than
10°C, the compressor will stop and not resume until
room temperature exceeds 13°C.
The evaporator anti-freezing protection is the same as
that in cooling mode.
1.9 Forced operation function
Forced cooling mode:
The compressor and outdoor fan continue to run and
the indoor fan runs at low speed. After running for 30
minutes, the AC will switch to auto mode with a preset
temperature of 24°C.
Forced auto mode:
Forced auto mode operates the same as normal auto mode
with a preset temperature of 24°C.
The unit exits forced operation when it receives the
following signals:
Switch on
Switch off
Timer on
Timer off
Changes in:
mode
fan speed
sleeping mode
1.10 Auto-Restart function
The indoor unit has an auto-restart module that
allows the unit to restart automatically. The module
automatically stores the current settings (not including
the swing setting) and, in the case of a sudden power
failure, will restore those setting automatically within 3
minutes after power returns.
If the unit was in forced cooling mode, it will run in
this mode for 30 minutes and turn to auto mode with

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea Forest MSAFC-18CRN1-NB8 and is the answer not in the manual?

Midea Forest MSAFC-18CRN1-NB8 Specifications

General IconGeneral
BrandMidea
ModelForest MSAFC-18CRN1-NB8
CategoryAir Conditioner
LanguageEnglish

Related product manuals