EasyManua.ls Logo

Midea LSBLG MCF Series

Midea LSBLG MCF Series
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Flooded type water cooled screw chiller (MIC) MCAC-CTSM-2018-1
38
Number of steps for valve closing
3970
Valve rate
250
Low SH protection: threshold
1
Low SH protection: integration time
2.5
LOP protection: threshold
-50
LOP protection: integration time
4
MOP protection: threshold
50
MOP protection: integration time
10
Low overheat degree alarm delay
(Low SH, 0 = no alarm)
300
Low evaporation temperature alarm
delay (LOP, 0 = no alarm)
300
High evaporation temperature alarm
delay (MOP, 0 = no alarm)
600
Low air suction temperature alarm
threshold
-50
Low air suction temperature alarm
delay (0 = no alarm)
300

Related product manuals