M‐ThermalSplit
20190955
4.10 H1Troubleshooting
Digitaldisplayoutput
Description
Communicationerrorbetweenoutdoorunitmaincontrolboardandinvertermodule.
M‐ThermalSplitstopsrunning.
ErrorcodeisdisplayedonoutdoorunitmainPCBanduserinterface.
Possiblecauses
Powersupplyabnormal.
Interferencefromasourceofelectromagneticradiation.
OutdoorunitmainPCBorinverterdrivenmoduledamaged.
Procedure
H1 


LEDonthemaincontrolboardof
outdoorunitandinvertermoduleare
light
Yes
LEDisnotlight,theboardis
damaged,orhaveshortcircuit
No

Communicatinwiresbetweenthemain
controlboardofoutdoorunitand
invertermoduleisloose
Yes
Reconnectthecommunicatinwires
No

Thereisasourceofelectromagnetic
radiationneartheunit,suchas
high‐frequencytransmitterorotherhigh
strengthradiationdevice
Yes
Removethesourceofinterference
No

ReplaceoutdoorunitmainPCBand
inverterdrivenmoduleinturn
